Simply disclose everything, every event, every parameter, on every cycle, all the time – within seconds

No longer will your power distribution system hold any secrets. The power recorder series is a unique range of instruments that increase your ability to maintain and troubleshoot your plant’s power quality. They monitor every aspect of power without blind spots or gaps, on all conductors in your 3-phase distribution system. 9 channels allow you to exactly monitor what’s happening on the neutral and ground conductors as well. Unlike other power monitors, every parameter on every conductor is measured all the time. And they are easy to use. Within seconds you will have your first measurements. There’s no need to set trigger thresholds or reconfigure the instrument. Just hook it up and start monitoring.

 

 

Features:

 

Software completes the system

 

Power Analysis System software

Plot events on any power tolerance curve. You can create your own or use CBEMA, ITIC and ANSI curves

For the Power Analysis System software there are two optional packages available:

Report writer software. This software analyzes all the data collected. It sorts events and summary data and merges graphs with Microsoft Word for easy documentation and report creation.

Polling and alarm software. This automates collection of data from multiple monitors to: alert key personnel to serious events by executing alarm procedures. easily centralize data collection via

 

The Scenario software

 

Specifications

Number of channels

Voltage channels:

 4

Current channels:

 5

Voltage (phase)

Range:

 100 mV - 600 VRMS, 1000 V peak

Sampling rate:

 6.4 kS/s¹ or 2 MS/s²

Resolution:

 14 bits, 90 mV

Accuracy:

 ±(1.5% of reading + 0.5 V)

Voltage (neutral)

Range:

 10 mV - 70 VRMS, 1000 V peak

Sampling rate:

 6.4 kS/s¹ or 2 MS/s²

Resolution:

 14 bits, 90 mV

Accuracy:

 ±(1.5% of reading + 0.5 V)

Current

Range:

 Depends upon CT

Sampling rate:

 6.4 kS/s¹

Resolution:

 14 bits

Accuracy:

 ±(0% of reading + 0.1% of probe range + probe uncertainty)

Transient Capture

Range:

 200 - 1000 V peak

Sampling rate:

 6.4 kS/s¹

Resolution:

 10 bits, 12 V

Accuracy:

 ±(5% of reading + 36 V)

High speed transient capture

Range:

 200 - 6400 V peak

Sampling rate:

 6.4 kS/s¹

Resolution:

 10 bits, 12 V

Accuracy:

 ±(5% of reading + 36 V)

Notes:

¹)

 50 Hz line frequency

²)

 For high speed models

 

 Nominal fundamental frequency: 50/60 Hz ± 0.1 Hz

 

 Voltage and current sampling: 128 samples per cycle

 

Environmental Specifications

Operating Temperature

 

 0 - 50 °C

Humidity (Without Condensation)

 

 90%

 

Safety Specifications

Safety Rating

 

 IEC 61010-1 CAT III 600 V

Standards:

Measurements:

 IEC 61000-4-30 Class B using cycle based techniques

Power Quality:

 EN 50160

 

Mechanical & General Specifications

Size

 

 21.25 x 30 x 7.5 cm

Weight

 

 6 kg

Warranty

 

 1 year

Case

 

 Rugged, aluminium casing

Power, battery life

Mains:

 85 - 264 VAC, 47 - 440 Hz

DC:

 10 - 15 V with 4255 Cable

Backup:

 NiCd, recharges automatically while power is applied

 

 Powers the instrument for 5 minutes then controlled shutdown. Monitoring resumes after power is restored.

Power Consumption:

 40 W

Communication

 

 10Base-T Ethernet, RJ45 connector or via Internet